CIPer MODEL 50 CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
Example 2: Multiple CIPer Model 50 Controllers and Connected BACnet Modules
Fig. 45. Connection of multiple CIPer Model 50 controllers via their RS485-1 interfaces to a BACnet MS/TP Bus
Example 3: Multiple CIPer Model 50 Controllers and Connected BACnet Modules (with
inserted termination resistor)
Fig. 46. Connection of multiple CIPer Model 50 controllers via their RS485-1 interfaces to a BACnet MS/TP Bus
The termination resistor must be inserted directly into the terminals of the last BACnet MS/TP module (in this example,
that is the rightmost CIPer Model 50, the 3-position slide switch of which has been set to "BIAS.")
31-00233EFS-01
36