Communication via Ethernet/IP (EIP)

7.7 Integrating the drive device into the EIP network via DHCP

7.7
Integrating the drive device into the EIP network via DHCP
Integrating the drive via the PROFINET onboard interface X150 into the EIP network
Proceed as follows to integrate the drive into the EIP network:
1. Set p8924 (PN DHCP mode) = 2 or 3
2. Save the settings with p8925 = 2.
The next time that it is run-up, the drive retrieves the IP address made available by a
DHCP server. After the drive has run-up, you can address the drive as Ethernet
participant.
Note
Immediate switchover without restart
The switchover to DHCP is performed immediately and without a restart if the change is
carried out with the EIP command "Set Attribute Single" (class F5 hex, attribute 3), e.g.
using:
• An EIP control
• An EIP commissioning tool
Result:
You have integrated the drive into the EIP network via DHCP.
Displays
● r8930: Station name of the onboard PROFINET interface X150
● r8934: DHCP mode of the onboard PROFINET interface X150
● r8935: MAC address of the onboard PROFINET interface X150
200
Parameterization
Meaning
p8924 = 2
The DHCP server assigns the IP address based on the MAC address.
p8924 = 3
The DHCP server assigns the IP address based on the station name.
Function Manual, 12/2018, 6SL3097-5BD00-0BP0