5.12
Support of I&M data sets 1...4
Identification & Maintenance (I&M)
I&M data sets contain information for a standardized and simplified identification and
maintenance of PROFIBUS/PROFINET devices. I&M data sets 1...4 contain plant-specific
information, such as the installation location and date. PROFINET supports I&M data sets
0...4.
I&M data sets 1...3 can be set with the SIMATIC Manager (STEP 7) and also with HW
Config (STEP 7).
I&M parameters
Table 5- 7
Parameter designation, assignment and meaning
I&M parameter
Format
designation
I&M 0:
-
IM_SUPPORTED
I&M 1:
Visible
TAG_FUNCTION
string
I&M 1:
Visible
TAG_LOCATION
string
I&M 2:
Visible
INSTALLATION_D
string
ATE
Communication
Function Manual, 12/2018, 6SL3097-5BD00-0BP0
Size/oct
Initialization
ets
-
-
32
Space
0x20...0x20
22
Space
0x20...0x20
16
Space
0x20...0x7E
5.12 Support of I&M data sets 1...4
SINAMICS
Meaning
parameters
r8820[62,63]
The parameter indicates which I&M data sets
are supported.
The value 0x1E indicates that I&M data sets
1...4 are available.
p8806[0...31]
Text that identifies the function or task of the
device.
p8806[32...53]
Text that identifies the device location.
p8807[0...15]
Text with the date of the installation or the
initial commissioning of the device. The fol-
lowing date formats are supported:
YYYY-MM-DD
YYYY-MM-DD hh:mm
YYYY: Year
MM: Month 01...12
DD: Day 01...31
hh: Hours 00...23
mm: Minutes 00...59
The separators between the individual speci-
fications, i.e. hyphen '-', blank ' ' and colon ':',
must be entered.
Communication via PROFINET IO
163