Mapping tables

Modbus register and Control Unit parameters
The Modbus protocol contains register or bit numbers for addressing memory. You must
assign the appropriate control words, status words, and parameters to these registers in the
device.
The valid holding register address range extends from 40001 up to 40722. When trying to
access other holding registers, the "Exception code" error is output
The process data are transferred into the register range from 40100 up to 40119.
Note
"R"; "W"; "R/W" in the "Access" column stands for read (with FC03); write (with FC06);
read/write.
Table 6- 1
Assigning the Modbus register to the parameters - process data
Register Description
Control data
40100
Control word (see SINAMICS S120/150
List Manual, function diagram 2442)
40101
Main setpoint
40102
STW 3
40103
STW 4
40104
PZD 5
40105
PZD 6
40106
PZD 7
40107
PZD 8
40108
PZD 9
40109
PZD 10
Status data
40110
Control word (see SINAMICS S120/150
List Manual, function diagram 2452)
40111
Main actual value
40112
ZSW 3
40113
ZSW 4
40114
PZD 5
40115
PZD 6
40116
PZD 7
40117
PZD 8
40118
PZD 9
40119
PZD 10
Communication
Function Manual, 12/2018, 6SL3097-5BD00-0BP0
Ac-
Unit
Scaling
cess
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R/W
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
R
-
1
Communication via Modbus TCP
6.4 Mapping tables
ON/OFF text
Data / parameter
or Value range
-
Process data 1
-
Process data 2
-
Process data 3
-
Process data 4
-
Process data 5
-
Process data 6
-
Process data 7
-
Process data 8
-
Process data 9
-
Process data 10
-
Process data 1
-
Process data 2
-
Process data 3
-
Process data 4
-
Process data 5
-
Process data 6
-
Process data 7
-
Process data 8
-
Process data 9
-
Process data 10