Communication according to PROFIdrive
3.4 Acyclic communication
Error
Meaning
value
0x7C
Parameter %s [%s]: Write access
only in the commissioning state,
device download (de-
vice: p0009 = 29).
0x7D
Parameter %s [%s]: Write access
only in the commissioning state,
device parameter reset (de-
vice: p0009 = 30).
0x7E
Parameter %s [%s]: Write access
only in the commissioning state,
device ready (device: p0009 = 0).
0x7F
Parameter %s [%s]: Write access
only in the commissioning state,
device (device: p0009 not equal to 0).
0x81
Parameter %s [%s] must not be writ-
ten during download.
0x82
Transfer of master control is blocked
by BI: p0806.
0x83
Parameter %s [%s]: Requested BICO
interconnection not possible.
0x84
Parameter %s [%s]: Parameter
change inhibited
(refer to p0300, p0400, p0922)
0x85
Parameter %s [%s]: Access method
not defined.
0x87
Write job will not be executed.
0xC8
Below currently valid limit.
0xC9
Above currently valid limit.
0xCC
Write access not permitted.
58
Remark
BICO output does not supply float values. The BICO input,
however, requires a float value.
The write request is rejected because know-how protection
is active.
Modification request for a value that, although within "abso-
lute" limits, is below the currently valid lower limit.
Modification request for a value that, although within "abso-
lute" limits, is above the currently valid upper limit (e.g. gov-
erned by the current converter rating).
Write access is not permitted because an access code is not
available.