Communication With Cbe20 - Siemens SINAMICS S120 Series Function Manual

Hide thumbs Also See for SINAMICS S120 Series:
Table of Contents

Advertisement

Overview of important parameters (see SINAMICS S120/S150 List Manual)
T
DC
T
CACF
T
I
T
O
5.5

Communication with CBE20

The CBE20 is a Communication Board that can be flexibly used and which can be operated
with different communication profiles. Only one firmware of a communication profile can be
loaded at any one time. The available firmware files are saved with the communication
profiles in UFW files on the Control Unit memory card. Firmware can only be selected prior
to commissioning.
The required file is selected using parameter p8835. A POWER ON must be carried out after
selecting the desired UFW file. During the subsequent system boot, the corresponding UFW
file is loaded. The new selection then becomes active.
Table 5- 5
Functionality (p8835)
PROFINET device
PROFINET Gate
SINAMICS Link
EtherNet/IP
Modbus TCP
Customer-specific
from OEM directory
Path for the UFW file and folders on the memory card: /OEM/SINAMICS/CODE/CB/CBE20.UFW
1)
Identification of the firmware version
Using parameter r8858, the loaded firmware version of the PROFINET interface can be
identified uniquely.
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p8835
• r8858[0...39]
• r8859[0...7]
Communication
Function Manual, 12/2018, 6SL3097-5BD00-0BP0
r2064[1]
PB/PN diagnostics isochronous operation: Bus cycle time
r2064[2]
PB/PN diagnostics isochronous operation: Master cycle time
r2064[3]
PB/PN diagnostics isochronous operation: Instant that the actual
value is acquired
r2064[4]
PB/PN diagnostics isochronous operation: Instant that the set-
point is acquired
Functionality and selection in the pointer file
Content
1
2
3
4
5
99
1)
CBE20 firmware selection
COMM BOARD read diagnostics channel
COMM BOARD identification data
Communication via PROFINET IO
5.5 Communication with CBE20
Detailed information on this is provided in Chapter:
-
"Communication via PROFINET Gate (Page 136)"