Annex 3: System Turn OFF Progress List

Tick after
No.
completion
1
2
3
4
5
Soft-off the PCS through PCS's control panel.
Turn off the switch between PCS and this battery string
(PowerCube-H1/H2), or turn off the power switch of
PCS, to make sure no current through this battery string.
Turn off all the "Power Switch" of the BMS.
Turn off the "Power Switch" of the MBMS.
Turn off the UPS. (If configured.)
The UPS can turn on to check the equipments (PCS
or battery system etc.). Otherwise must turn off the
UPS to save its power.