Siemens SINAMICS G130 Operating Instructions Manual page 52

Operator panel
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Maintenance and servicing
6.1 Replacing the backup battery
1. Disconnect the 24 V DC power supply cable.
2. Disconnect the communication cable on the operator panel.
3. Open the cover of the battery compartment.
4. Remove the old battery.
5. Insert the new battery.
6. Carry out any other work by reversing the sequence.
Table 6- 1
Type
Manufacturer
Nominal capacity
Self-discharge at 20 °C
Service life (in backup mode)
Service life (in operation)
Note
Replace battery within one minute
The battery must be replaced within one minute to ensure that no AOP settings are lost.
Note
Battery disposal
The battery must be disposed of in accordance with the applicable country-specific
guidelines and regulations.
50
Technical specifications of the backup battery
CR2032 3 V lithium battery
Maxell, Sony, Panasonic
220 mAh
1 %/year
> 1 year at 70 °C; >1.5 years at 20 °C
> 2 years
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A