This example shows an Inhibitor Pump
with 'Bleed then Feed' Special Control
Key DOWN to Configure and key ENTER
Key UP DOWN to view available Special Controls
Meter controlled relays do not have Special Controls
No Control & sensor controlled relays can select from:
Bleed & Feed, Bleed then Feed, Captured Sample,
% Time, Prebleed-Lockout, Time Modulation,
Holding Time and Time Modulation
Key ENTER to view, modify current Special Control
Key ENTER to modify the Bleed Relay
For every 5 minutes of Tower Bleed time,
the Inhibitor runs for 46% or 136 seconds
Key ENTER to modify the % of Time
This example increase the % of time from 46% to 52%
Special Controls are detailed in the on-line
M714_Tech, technical service manual
M714_User_Master.doc
Updated Aug. 25, 2015
then key DOWN to Special Control
Displays current special control
Or DOWN to view the % of Time
In this Bleed Then Feed example:
AFTER the bleed turns OFF
S e l e c t i n g S p e c i a l C o n t r o l s
3 . 9
.
.
Key ENTER
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Inhibitor Pump
OFF: No Control
Biocide A
ON:
8.6 min
Inhibitor Pump
Diagnostics
Configure
Alarms
then
Inhibitor Pump
Configure...........
Special Control
Bleed then Feed
and
Inhibitor Pump
Bleed then Feed-----
Bleed Relay
Tower Bleed
Inhibitor Pump
Bleed then Feed-----
% of Time
46%
then
Editing Value:
% of Time...........
52%
--
Executes
43
1
3
1
1
1
1
Exits