Controls
Alarms – Feed Limit Timers
Variable Cycles
Feed Verification
(Option)
Data Logging
Log Content
Log Size
Logging Rate
Log File Format
XML
System
Controller Configuration
Watchdog
Field Upgrades
M714_User_Master.doc
Updated Aug. 25, 2015
4 . 3
Rating - Detail
Minutes / Actuation
Minutes / Day
User defined trip alarm relay,
and/or dial-out
Three user defined ranges of
make-up conductivity and target
cycles.
User defined maximum tower
conductivity.
ppm calculation based on volume
fed and cycles of concentration.
Alarm on fail to feed.
User selected cycles method:
Fixed, Ratio of Tower/Makeup
conductivity, Ratio of
Makeup/Bleed Volume.
Rating - Detail
Analog Inputs: Min, Max & Average
Digital -Water Meters: Volume
Digital-Contact Set: ON Time
600 entries for each of 26 analog
and digital inputs and each of 10
relay outputs
21,600 Entries Total
User set independently for each
I/O from 5 to 1440 minutes / entry
User defined start & end date for
XML download
Rating - Detail
User selected Save and Restore to
FLASH memory
1 sec. Hardware relay lockout
Enable ETHERNET, Feed
Verification.
Add Sensors and Drivers
S p e c i f i c a t i o n s
User defined OFF on Feed Limit
Auto reset on Bleed & Feed and
Bleed then Feed
Requires control by the ratio of
analog sensors.
1% deadband on cycles and
maximum conductivity
Requires feed volume meter or
4-20mA input on feed rate.
Fail-to-to feed is no volume fed
after 30 seconds
Year to date included for Meters
600 entries = 25 Days
at 60 minutes Logging Rate
Default 60 minutes
.dtd defines date stamping for
each of 21,600 log entries
Makes current configuration
factory default.
Active on power up and
firmware blocked
Upgrades locked to Serial# and
date limited.
53
3 o f 4
Notes
Notes
Notes