Fixed Cycles applies a user set cycles
ppm is calculated using 3.5 cycles of concentration
Key UP DOWN and RIGHT to modify
Increasing the concentration from 3.5 to 4.23
Feed Verification must be set to YES in the Inhibitor pump control Configure menu option
Cycles of concentration is calculated using ratio of the Make-up to Bleed meter volumes
Cycles of concentration is calculated using ratio of the Tower to Make-up conductivities
M714_User_Master.doc
Updated Aug. 25, 2015
3 . 1 1 M o d i f y i n g F e e d V e r i f i c a t i o n
to calculate ppm
Key ENTER to view-modify cycles
Key ENTER to modify
increases the calculated ppm.
The Inhibitor pump relay must be controlled by the make-up water meter.
A fail-to-feed alarm is set on the feed verification meter input if the meter
does not measure volume after the pump has been ON for 30 seconds
Meter Cycles ppm calculation requires a water meter on the tower bleed.
Bleed Cycles ppm calculation requires the conductivity of the tower make-up.
.
.
.
.
.
.
.
.
.
.
.
.
then ENTER
.
.
Select one:
ppm method select...
Fixed Cycles
Executes
Inhibitor Pump
ppm method select---
Fixed Cycles
3.500 cycles
Inhibitor Pump
Fixed Cycles........
4.230 cycles
--
Executes
Feed Verification Primer
47
2 o f 2
Exits
1
1
Exits