ProMinent multiFLEX M10 User Manual page 18

Table of Contents

Advertisement

You can 'Prebleed' until this sensor measures
This is the 'Prebleed' conductivity target
'Prebleed' ends at this conductivity
Set high to control on 'Prebleed Time' only
All Prebleed-Lockout parameters are modified
by ENTER when the parameter is displayed
Key UP DOWN & RIGHT to modify
Bleed solenoid or valve now turns ON
For 45 minutes before each feed event
on Biocide A, powered by Relay No.3
M714_User_Master.doc
Updated Aug. 25, 2015
S e t t i n g B i o c i d e P r e b l e e d - L o c k o u t
2 . 1
the conductivity that you set
Key ENTER to modify
OR at the end of 'Prebleed Time'
Key ENTER to modify
then key ENTER
.
Biocide A
Prebleed-Lockout----
Prebleed Sensor
.
Tower Conduct'ty
.
.
Biocide A
.
Prebleed-Lockout----
Prebleed Value
.
750.0 uS
Typical: Modify Bleed time
.
Biocide A
.
.
Prebleed-Lockout----
Prebleed time
30.0 minutes
.
.
.
.
Editing Value:
.
.
Prebleed Time.......
45.0 minutes
--
Executes,
.
.
.
.
.
Biocide A
.
Prebleed-Lockout----
Prebleed time
45.0 minutes
.
.
2 o f 2
3
3
3
Exits
then
3
18