less than High Range & greater than Med. Range
Key ENTER to modify the High Cycles
When the Tower Conductivity exceeds
Bleed is controlled at Max Conductivity
Key ENTER to modify the Maximum Conductivity
Variable Cycles must be set to YES in the Bleed control Configure menu option
Example: Control Equation is E/F where E = Tower Conductivity & F = Makeup Conductivity.
The Control Equation may be modified in the Bleed control Configure menu option
M714_User_Master.doc
Updated Aug. 25, 2015
3 . 1 0 M o d i f y i n g V a r i a b l e C y c l e s
Key ENTER to modify High Range
When the Make-up Conductivity is
Bleed is controlled at High Cycles
Maximum Conductivity the
Variable Cycles modifies bleed setpoints as make-up conductivity changes
Setpoint adjustment is blocked when Variable Cycles is controlling.
Bleed Setpoint units are set to 'cycles' when Variable Cycles are selected.
You will need to modify the Range and Cycle Setpoints for your site
.
.
.
.
.
.
.
.
.
.
.
.
.
.
The bleed relay must be controlled by a conductivity ratio.
makeup water chemistry and water treatment program
Tower Bleed
Variable Cycles.....
High Range
1000 uS
or
Tower Bleed
Variable Cycles.....
High Cycles
2.500 cycles
or
Tower Bleed
Variable Cycles.....
Max Conduct.
3000 uS
or