Advertisement

Using Counters (C)
Note
3-7-2

Settings in the Parameter Settings Screen

Counter address
3-7-3

Parameter Monitor Screen Display

Count input status
( : OFF/ : ON)
Counter direction specification
input status ( : OFF/ : ON)
Note
Reset input
R (RES) When the reset input turns ON, the present
Turns ON when the counter has counted out (PV ≥ SV)
Count input
Only C0 to C7 (8 points) are supported by pre-V1 CPU Units.
Set value
0001 to 9999 (4 decimal digits) times
Monitor enabled/
A
disabled
D
Counter present value
RUN
1.
To reset the counter present value and counter bit status (ON/
OFF) when at power interruptions or when the operating mode is
changed, create a counter reset circuit when you first execute the
program. An example is shown below.
2.
If the counter input and counter direction are input simultaneous-
ly, place the output for the counter direction before the output for
the counter input in the program.
value returns to 0 and the counter bit turns
OFF. Count inputs are not accepted while the
reset input is ON.
Monitor enabled/disabled
Set value
Operating parameters can be monitored and
settings changed.
Operating parameters cannot be monitored or
settings changed.
Counter bit status ( : OFF/ : ON)
Counter setting
Reset input status
( : OFF/ : ON)
Counter reset
output
Counter direction specification output
Output to counter input
Section 3-7
71