Download Print this page
Omron G9SA Datasheet

Omron G9SA Datasheet

Safety relay unit
Hide thumbs Also See for G9SA:

Advertisement

Quick Links

Safety Relay Unit
G9SA
• Four kinds of 45-mm wide Units are
available:
A 3-safety contact model, a 5-safety
contact model, and models with 3 safe-
ty contacts and 2 OFF-delay safety
contacts.
Also available are 17.5-mm wide Ex-
pansion Units with 3 safety contacts
and 3 OFF-delay safety contacts.
• Two hand controller (type III C, EN 574)
• Simple expansion connection.
• OFF-delay models have 15-step OFF-
delay settings.
• Conforms to EN standards. (BG ap-
proval)
• Approved by UL and CSA.
• Both DIN track mounting and screw
mounting are possible.
• Suitable for PNP OSSD outputs of
safety sensors, F3SN, F3SH, F3S-B,
F3S-TGR, F3SL
Ordering Information
Emergency-stop Units
Main contacts
Auxiliary contact
3PST-NO
SPST-NC
5PST-NO
SPST-NC
Emergency-stop OFF-delay Units
OFF-delay
Main contacts
contacts
3PST-NO
DPST-NO
Note: The following 15-step OFF-delay time settings are available:
T075: 0.5, 1, 1.5, 2, 2.5, 3, 3.5, 4, 4.5, 5, 5.5, 6, 6.5, 7, and 7.5 s
T15: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, and 15 s
T30: 2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, and 30 s
Two-hand Controller
Main contacts
Auxiliary contact
3PST-NO
SPST-NC
Expansion Unit
The Expansion Unit connects to a G9SA-301, G9SA-501, G9SA-
Main contacts
3PST-NO
G9SA
The G9SA Series Offers a Complete
Line-up of Compact Units.
Number of input channels
1 channel or 2 channels possible
1 channel or 2 channels possible
Auxiliary
Number of
contact
input channels
1 channel
SPST-NC
or 2 channels
possible
Number of input channels
2 channels
Auxiliary contact
SPST-NC
Rated voltage
24 VAC/VDC
100 to 240 VAC
24 VAC/VDC
100 to 240 VAC
OFF-delay
Rated voltage
time
24 VAC/VDC
7.5 s
100 to 240 VAC
24 VAC/VDC
15 s
100 to 240 VAC
24 VAC/VDC
30 s
100 to 240 VAC
Rated voltage
24 VAC/VDC
100 to 240 VAC
321, or G9SA-TH301.
Model
G9SA-EX301
Model
Category
G9SA-301
4
G9SA-501
Model
Category
G9SA-321-T075 Main contacts:
4
G9SA-321-T15
OFF-delay
contacts:
3
G9SA-321-T30
Model
Category
G9SA-TH301
4 (IIIc, EN574)
Category
4
G-109

Advertisement

loading

Summary of Contents for Omron G9SA

  • Page 1 Note: The following 15-step OFF-delay time settings are available: T075: 0.5, 1, 1.5, 2, 2.5, 3, 3.5, 4, 4.5, 5, 5.5, 6, 6.5, 7, and 7.5 s T15: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, and 15 s...
  • Page 2 Note: The following 15-step OFF-delay time settings are available: T075: 0.5, 1, 1.5, 2, 2.5, 3, 3.5, 4, 4.5, 5, 5.5, 6, 6.5, 7, and 7.5 s T15: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, and 15 s...
  • Page 3: Specifications

    Note: 1. The contact resistance was measured with 1 A at 5 VDC using the voltage-drop method. 2. The response time is the time it takes for the main contact to open after the input is turned OFF. 3. The insulation resistance was measured with 500 VDC at the same places that the dielectric strength was checked.
  • Page 4: Application Examples

    Application Examples G9SA-301 (24 VAC/VDC) with 2-channel Limit Switch Input/Auto-reset Timing Chart Limit switches S1 and S2 K1 and K2 (NC) K1 and K2 (NO) Feedback loop KM1 and KM2 (NC) KM1 and KM2 (NO) Open Safety Limit Switch with direct opening mechanism...
  • Page 5 G9SA-301 (100 to 240 VAC) with 2-channel Limit Switch Input/Auto-reset Timing Chart Limit switches S1 and S2 K1 and K2 (NC) K1 and K2 (NO) Feedback loop KM1 and KM2 (NC) KM1 and KM2 (NO) Open Safety Limit Switch Control...
  • Page 6 G9SA-321-T# (24 VAC/VDC) with 2-channel Limit Switch Input/Manual-reset Feedback loop Open Off delay Control timer circuit Safety Limit Switch with direct opening mechanism Operation (D4N or D4B) instruction Motor controller Limit switch Reset switch KM1 and KM2: Magnetic Contactor 3-phase motor...
  • Page 7 G9SA-321-T# (24 VAC/VDC) + G9SA-EX031-T# with 2-channel Limit Switch Input/Manual-reset Feedback loop Open Off delay timer Off delay Control timer circuit Safety Limit Switch with direct opening mechanism (D4N or D4B) Limit switch Operation Reset switch instruction KM1, KM2, Motor controller...
  • Page 8 G9SA-301 (24 VAC/VDC) with 2-channel Safety Area Sensor/Manual-reset Timing Chart F3SN-A Incident Interrupted Reset switch S1 K1 and K2 Emitter Receiver (NC) K1 and K2 (NO) KM1 and KM2 (NC) KM1 and KM2 (NO) PC input F3SN-A F3SH-A PC output...
  • Page 9 0.5 s max. S11, S12: Two-hand pushbutton switches KM1 and KM2: Magnetic Contactor Control circuit Note: 1. Use a 1NC+1NO switch for S11 and S12. 2. This circuit achieves EN954-1 Safety Category 4. Typ III C (EN 574)
  • Page 10 G9SA-501 (24 VAC/VDC) and G9SA-EX301 with 2-channel Limit Switch Input/Manual-reset Feedback loop Open Control circuit Safety Limit Switch with direct opening mechanism (D4N or D4B) Limit switch Reset switch KM1 and KM2: Magnetic Contactor 3-phase motor Timing Chart Limit switches S1...
  • Page 11 Dimensions Note: All units are in millimeters unless otherwise indicated. The diagrams are drawn in perspective. G9SA-301 G9SA-501 G9SA-321-T# Terminal Arrangement G9SA-TH301 G9SA-301 G9SA-501 G9SA-TH301 G9SA-321-T# OFF- delay time setting switch (see note) G9SA-301: Twenty, M3 Mounting Holes G9SA-501: Twenty-four, M3 G9SA-321-T#: Twenty-four, M3 Two, 4.2 dia.
  • Page 12: Installation

    13 23 33 41 open. For 1-channel input, make sure T12 and T23 are closed. 4. With 100 to 240-VAC type, be sure to connect PE to a protective ground. With 24-VAC/VDC type, if the power Off delay supply is not connected to a protective ground, be sure timer to connect PE to a protective ground.
  • Page 13 Solid wire: 1.0 to 1.5 mm meets EN954-1 requirements. Tighten each screw to a torque of 0.78 to 1.18 N·m, or the G9SA Mounting Multiple Units may malfunction or generate heat. When mounting multiple Units close to each other, the rated current External inputs connected to T11 and T12 or T21 and T22 of the will be 3 A.
  • Page 14 ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. Cat. No. J121-E2-03A-X In the interest of product improvement, specifications are subject to change without notice. G-122 Safety Sensors / Components...