Dip Switch Settings - Omron K8AK-VW Manual

Single-phase overvoltage/undervoltage relay
Hide thumbs Also See for K8AK-VW:
Table of Contents

Advertisement

K8AK-VW
Operation Methods
Setting Ranges and Wiring Connections
Model
Setting range
1 to 10 V AC/DC
K8AK-VW2
3 to 30 V AC/DC
15 to 150 V AC/DC
20 to 200 V AC/DC
K8AK-VW3
30 to 300 V AC/DC
60 to 600 V AC/DC
Connections
●Input
Connect the input between terminals V1-COM, V2-COM, or V3-COM, depending on the input
voltage.
Malfunctions may occur if the input is connected to unused terminals and the Unit will not operate
correctly.
●Power Supply
Connect the power supply to terminals A1 and A2.
●Outputs
AL1 (SPDT relay) is output to terminals 11, 12, and 14.
AL2 (SPDT relay) is output to terminals 21, 22, and 24.
Note: Use the recommended ferrules if using twisted wires.

DIP Switch Settings

The power ON lock time, resetting method and operating mode are set using the DIP switch located on the bottom of the Unit.
OFF
ON
SW4
SW3
DIP switch pins
SW2
SW1
6
Wiring connection
V1-COM
V2-COM
V3-COM
V1-COM
V2-COM
V3-COM
●DIP Switch Functions
Pin
1 s
Power ON
lock time
5 s
Manual reset
Resetting
method
Operating mode
AL1
AL2
Overvoltage
Undervoltage
Operating
Overvoltage
Overvoltage
mode
Undervoltage
Undervoltage
Overvoltage
Undervoltage
Note: All pins are set to OFF at the factory.
Single-phase power
Load
OFF ● ↑
1
2
OFF
ON ❍ ↓
ON
---
---
---
---
---
---
---
---
---
---
---
---
A1
Power supply
voltage
A2
V1
Voltage input
C (COM)
V2
V3
14
11
Signal output
AL1 relay
12
signal
output
24
21
Signal output
AL2 relay
22
signal
output
3
4
---
---
---
---
---
---
---
---