13 Safety notes for the installation according UL

Markings:
Wiring terminal markings:
See markings on the enclosure and the corresponding chapters in the installation guide!
Cautionary Marking:
See markings on the enclosure and the corresponding chapters in the installation guide!
Motor overload protection must be provided externally in the end-use. Motor Overload protection can
alternatively be provided when the connected motor has a thermal sensor rated 5V DC, max. 100mA
which is connected to the drive thermal sensor input (X3). (The LinMot P01-Motors are therefore
protected by the drive)
The transients have to be limited to max. 0.8kV on the line side of the drive.
The 24VDC supply for the control circuit must be protected with an external UL Listed 3A DC Fuse.
Proposed ratings, to be evaluated in the end-use:
Input Voltage:
Input current:
Output Voltage:
Output Current:
Number of Phases:
Frequency range:
Duty cycle rating:
Relays (only for -1S variant):
Rated Contacts:
Coil:
Surrounding air temp:
Control Power (X4-2):
Surrounding Air Temperature: max. 50°C
A separate 24VDC power supply protected with an external UL Listed 3A DC Fuse connected to
the output of the power supply must be used to protect the secondary control circuit (safety
relays on X33)
NTI AG / LinMot
72VDC
15A
61.5V rms
17.7A rms max.
2 by 1 Phase
0-500Hz
10%
max. 24VDC 6A.
24VDC
max. 85°C
24VDC (Protected with an external UL Listed 3A DC Fuse)
0185-1062-E_6V12_IG_Drives_C1100
Page 21 of 29