Control Board; Control Connections - WEG MW500 User Manual

Hide thumbs Also See for MW500:
Table of Contents

Advertisement

Available languages

Available languages

3.2.5 Control Board

Plug-in modules are connected to control board. S10 DIP-switch are available in control board,
for more information refer to

3.2.6 Control Connections

The control connections (analog input/output, digital input/output and interface RS-485) must
be performed according to the specification of the connector of the plug-in module connected
to the MW500. Refer to the guide of the plug-in module in print. The typical functions and
connections for the CFW500-IOS standard plug-in module are shown in
15. For further details about the specifications of the connector signals, refer to
TECHNICAL SPECIFICATIONS on page
(*) Digital input 2 (DI2) can also be used as input in frequency (FI). For further details refer to the programming manual of the MW500.
(**) For further information, refer to the detailed specification in
Figure 3.4: Signals of the connector of the CFW500-IOS plug-in module
The location of the plug-in module and DIP-switches to select the type of analog input and
output signal and the termination of the RS-485 network is shown in
The MW500 inverters are supplied with the digital inputs configured as active low (NPN), analog
input and output configured for signal in voltage 0...10 V and with the termination resistor of
the RS-485 OFF.
Section 4.3 OPERATING MODES OF THE HMIR on page
35.
Section 8.2 ELECTRONICS/GENERAL DATA on page
Installation and Connection
Figure 3.4 on page
Connector
Description
1
DI1
Digital input 1
3
DI2
Digital input 2
5
DI3
Digital input 3
7
DI4
Digital input 4
9
+24 V
Power supply +24 Vdc
Digital output 1
11
DO1-RL-NO
(Relay NO contact 1)
Digital output 1
13
DO1-RL-C
(Relay common point 1)
Digital output 1
15
DO1-RL-NC
(Relay NC contact 1)
2
AO1
Analog output 1
4
GND
Reference 0 V
6
AI1
Analog input 1
Reference +10 Vdc for
8
+10 V
potentiometer
10
DO2-TR
Digital output 2 (Transistor)
12
RS-485 - A
RS-485 (Terminal A)
14
RS-485 - B
RS-485 (Terminal B)
16
GND
Reference 0 V
36.
Figure A.1 on page
21.