Powering up and Start-up
Seq
Indication on the Display / Action
13
If necessary, modify the content of "P0407 - Motor
Rated Power Factor", or press the key
next parameter
15
D u r i n g th e S e l f-Ad j u s tm e n t th e H M I R w i l l
simultaneously indicate the status of "RUN" and
"CONF". And the bar graph indicates the progress
of the operation
And the bar graph indicates the progress of the
operation. The Self-Adjustment can be interrupted
at any time by means of the key
17
The result of Self-Adjustment is the value in ohms of
the motor stator resistance shown in P0409
This is the last parameter of the Self-Adjustment of
the V V W control mode. Press the key
to initial parameter P0202
19
Through the keys
menu or press the key BACK/ESC again to return
directly to the monitoring mode of the HMIR
28 | MW500
for the
to return
and
, select the desired
Figure 5.5: Sequence of the Start-up group for V V W control
Seq
Indication on the Display / Action
14
At this point, the HMIR shows the option to do
the self-adjustment. Whenever possible, perform
the self-adjustment. Thus, to activate the self-
adjustment, change the value of P0408 to "1"
16
At the end of the Self-Adjustment, the value of
P0408 automatically returns to "0", as well as the
Status of "RUN" and "CONF" are cleared
Press the key
for the next parameter
18
To exit the STARTUP menu, just press BACK/ESC