Danfoss VLT HVAC Basic Drive FC 101 Quick Manual page 47

Hide thumbs Also See for VLT HVAC Basic Drive FC 101:
Table of Contents

Advertisement

Quick Guide
A)
Digital output
Number of digital outputs
Terminal number
Voltage level at digital output
Max. output current at digital output
Max. load at digital output
1) Terminals 42 and 45 can also be programmed as analog output.
Control card, RS-485 serial communication
Terminal number
Terminal number
Control card, 24 V DC output
Terminal number
Max. load
Relay output
Programmable relay output
Relay 01 and 02
1)
Max. terminal load (AC-1)
on 01-02/04-05 (NO) (Resistive load)
Max. terminal load (AC-15)
1)
on 01-02/04-05 (NO) (Inductive load @ cosφ 0.4)
1)
Max. terminal load (DC-1)
on 01-02/04-05 (NO) (Resistive load)
1)
Max. terminal load (DC-13)
on 01-02/04-05 (NO) (Inductive load)
1)
Max. terminal load (AC-1)
on 01-03/04-06 (NC) (Resistive load)
Max. terminal load (AC-15)
1)
on 01-03/04-06 (NC) (Inductive load @ cosφ 0.4)
1)
Max. terminal load (DC-1)
on 01-03/04-06
(NC) (Resistive load)
Environment according to EN 60664-1
1)
IEC 60947 parts 4 and 5.
A)
Control card, 10 V DC output
Terminal number
Output voltage
Max. load
A)
All inputs, outputs, circuits, DC supplies and relay contacts are galvanically isolated from the supply voltage (PELV) and
other high-voltage terminals.
MG18A522
Quick Guide
A)
Min. terminal load on 01-03 (NC), 01-02 (NO) 24 V DC 10 mA, 24 V AC 20 mA
Danfoss A/S © Rev. 2014-01-22 All rights reserved.
68 (P, TX+, RX+), 69 (N, TX-, RX-)
61 Common for terminals 68 and 69
01-03 (NC), 01-02 (NO), 04-06 (NC), 04-05 (NO)
Overvoltage category III/pollution degree 2
1
1
2
1)
42, 45
17 V
20 mA
1 kΩ
12
80 mA
2
250 V AC, 3 A
250 V AC, 0.2 A
30 V DC, 2 A
24 V DC, 0.1 A
250 V AC, 3 A
250 V AC, 0.2 A
30 V DC, 2 A
50
10.5 V ±0.5 V
25 mA
45

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT HVAC Basic Drive FC 101 and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents