Quick Guide
1
1
Power (hp [kW])
Frame
I2
I3
I4
I6
I7
I8
Table 1.8 Enclosure I1-I8
Power (hp [kW])
Frame
H9
H10
H6
H7
H8
Table 1.9 Details of Tightening Torques
1
Cable dimensions
2
Cable dimensions >0.1472 in
1.3.4 Connecting to Line Power and Motor
The adjustable frequency drive is designed to operate all standard three-phased asynchronous motors. For maximum cross-
section on wires, see chapter 1.7 General Specifications.
•
Use a shielded/armored motor cable to comply with EMC emission specifications, and connect this cable to both
the decoupling plate and the motor metal.
•
Keep motor cable as short as possible to reduce the noise level and leakage currents.
•
For further details on mounting of the decoupling plate, see FC 101 Decoupling Plate Mounting Instruction.
•
Also see EMC-Compatible Installation in the VLT
1.
Mount the ground wires to the ground terminal.
2.
Connect the motor to terminals U, V and W.
3.
Mount line power supply to terminals L1, L2 and L3 and tighten.
8
IP class
3x380–480 V
IP54
1– 5 [0.75–4.0]
12.39 [1.4]
IP54
7.5–10 [5.5–7.5]
12.39 [1.4]
IP54
15–25 [11–18.5]
12.39 [1.4]
IP54
30–50 [22–37]
0.18 [4.5]
IP54
60–75 [45–55]
88.51 [10]
IP54
100–125 [75–90] 123.91/212.42
[14/24]
IP class
3x525–600 V
IP20
3–10 [2.2–7.5]
15.93 [1.8]
IP20
15–20 [11–15]
15.93 [1.8]
IP20
25–40 [18.5–30]
0.18 [4.5]
IP20
50–75 [37–55]
88.51 [10]
IP20
100–125 [75–90] 123.91/212.42
[14/24]
≤ 0.1472 in
2
[95 mm
2
]
2
[95 mm
2
]
Danfoss A/S © Rev. 2014-01-22 All rights reserved.
Quick Guide
Line
Motor
connection
7.08 [0.8]
7.08 [0.8]
7.08 [0.8]
7.08 [0.8]
7.08 [0.8]
7.08 [0.8]
0.18 [4.5]
88.51 [10]
123.91/212.42
1
1
[14/24]
Line
Motor
connection
15.93 [1.8]
recommended
15.93 [1.8]
recommended
0.18 [4.5]
88.51 [10]
123.91/212.42
1
1
[14/24]
®
HVAC Basic Design Guide.
Torque (in-lb [Nm])
DC
Control
Ground
terminals
4.43 [0.5]
7.08 [0.8]
4.43 [0.5]
7.08 [0.8]
4.43 [0.5]
7.08 [0.8]
-
4.43 [0.5]
26.55 [3]
-
4.43 [0.5]
26.55 [3]
-
4.43 [0.5]
26.55 [3]
Torque (in-lb [Nm])
DC
Control
Ground
terminals
Not
4.43 [0.5]
26.55 [3]
Not
4.43 [0.5]
26.55 [3]
-
4.43 [0.5]
26.55 [3]
-
4.43 [0.5]
26.55 [3]
-
4.43 [0.5]
26.55 [3]
Relay
4.43 [0.5]
4.43 [0.5]
4.43 [0.5]
5.31 [0.6]
5.31 [0.6]
5.31 [0.6]
Relay
5.31 [0.6]
5.31 [0.6]
4.43 [0.5]
4.43 [0.5]
4.43 [0.5]
MG18A522