Quick Guide
Parameter
1-20 Motor Power
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal Speed
1-26 Motor Cont. Rated Torque
1-29 Automatic Motor Adaption
(AMA)
1-30 Stator Resistance (Rs)
1-37 d-axis Inductance (Ld)
1-39 Motor Poles
1-40 Back EMF at 1000 RPM
1-73 Flying Start
1-73 Flying Start
3-02 Minimum Reference
3-03 Maximum Reference
3-41 Ramp 1 Ramp Up Time
3-42 Ramp 1 Ramp Down Time
4-12 Motor Speed Low Limit [Hz]
4-14 Motor Speed High Limit [Hz]
4-19 Max Output Frequency
5-40 Function Relay [0] Function
relay
5-40 Function Relay [1] Function
relay
6-10 Terminal 53 Low Voltage
MG18A522
Quick Guide
Option
0.12–110 kW/0.16–150 hp
50.0–1000.0 V
20.0–400.0 Hz
0.01–10000.00 A
100.0–9,999.0 RPM
0.1–1000.0
See 1-29 Automatic Motor
Adaption (AMA)
0.000–99.990
0–1000
2–100
10–9000
[0] Disabled
[1] Enabled
-4999–4999
-4999–4999
0.05–3600.0 s
0.05–3600.0 s
0.0–400 Hz
0.0–400 Hz
0-400
See 5-40 Function Relay
See 5-40 Function Relay
0–10 V
Danfoss A/S © Rev. 2014-01-22 All rights reserved.
Default
Function
Size related
Enter motor power from nameplate data
Size related
Enter motor voltage from nameplate data
Size related
Enter motor frequency from nameplate data
Size related
Enter motor current from nameplate data
Size related
Enter motor nominal speed from nameplate
data
Size related
This parameter is available only when
1-10 Motor Construction Design is set to [1]
PM, non-salient SPM.
NOTICE!
Changing this parameter will affect
settings of other parameters
Off
Performing an AMA optimizes motor
performance.
Size related
Set the stator resistance value
Size related
Enter the value of the d-axis inductance.
Obtain the value from the permanent magnet
motor data sheet. The de-axis inductance
cannot be found by performing an AMA.
4
Enter the number of motor poles
Size related
Line-Line RMS back EMF voltage at 1000 RPM
When PM is selected, Flying Start is enabled
and cannot disable
0
Select [1] Enable to enable the drive to catch
a motor spinning due to line drop-out. Select
[0] Disable if this function is not required.
When is enabled 1-71 Start Delay and
1-72 Start Function have no function. is active
plus
in VVC
mode only
0
The minimum reference is the lowest value
obtainable by summing all references.
50
The maximum reference is the lowest
obtainable by summing all references.
Size related
Ramp-up time from 0 to rated 1-23 Motor
Frequency if Asynchron motor is selected;
ramp-up time from 0 to 1-25 Motor Nominal
Speed if PM motor is selected
Size related
Ramp-down time from rated 1-23 Motor
Frequency to 0 if Asynchron motor is selected;
ramp-down time from 1-25 Motor Nominal
Speed to 0 if PM motor is selected.
0 Hz
Enter the minimum limit for low speed
65 Hz
Enter the maximum limit for high speed
Size related
Enter the maximum output frequency value
Alarm
Select the function to control output relay 1.
Drive running
Select the function to control output relay 2.
0.07 V
Enter the voltage that corresponds to the low
reference value.
1
1
25