CAUTION! (ONLY FOR AUSTRALIAN MACHINES)
THIS MACHINE MUST BE INSTALLED BY AUTHORISED PERSONNEL IN ACCORDANCE WITH THIS
INSTRUCTION MANUAL, AS/NZS 5601-GAS INSTALLATIONS (INSTALLATION AND PIPE SIZING)
REGULATIONS, LOCAL GAS FITTING REGULATIONS, LOCAL WATER REGULATIONS, LOCAL
HEALTH REGULATIONS, THE BUILDING CODE OF AUSTRALIA AND ANY OTHER GOVERNMENT
AUTHORITY.
NATURAL GAS: THE SUPPLIED REGULATOR MUST BE FITTED TO THE MACHINE INLET
CONNECTION. GAS PRESSURE MUST BE ADJUSTED TO 0.7 kPa WHEN THE BURNER IS
OPERATING. THE APPLIANCE TEST POINT IS LOCATED ON THE COMBINATION CONTROL.
GAS LPG: GAS PRESSURE MUST BE ADJUSTED TO 2.50 kPa WHEN THE BURNER IS OPERATING.
THE APPLIANCE TEST POINT IS LOCATED ON THE COMBINATION CONTROL.
CAUTION! (ONLY FOR ETL CERTIFIED MACHINES)
THIS MACHINE MUST BE INSTALLED BY AUTHORISED PERSONNEL IN ACCORDANCE WITH LOCAL
CODES OR, IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL FUEL GAS CODE, ANSI
Z223.1/NFPA 54 OR THE NATURAL GAS AND PROPANE INSTALLATION CODE, CSA B149.1.
THE DRYER AND ITS MANUALLY OPERATED APPLIANCE MAIN GAS VALVE MUST BE
DISCONNECTED FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY PRESSURE TESTING OF
THAT SYSTEM AT TEST PRESSURES IN EXCESS OF ½ PSI (3.5 KPA).
THE DRYER MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING THE
EQUIPMENT SHUT-OFF VALVE DURING ANY PRESSURE TESTING OF THE GAS SUPPLY PIPING
SYSTEM AT TEST PRESSURES EQUAL TO OR LESS THAN ½ PSI (3.5 KPA).
A MINIMUM 1/8 IN NPT PLUGGED TAPPING, ACCESSIBLE FOR TEST GAGE CONNECTION, MUST BE
INSTALLED IMMEDIATELY UPSTREAM OF THE GAS SUPPLY CONNECTIONS TO THE DRYER.
Connecting the machine
53