3.6. Ventilation conditions and extraction in the premises

CAUTION!
THE VENTILATION IN THE PREMISES MUST COMPLY WITH THE REGULATIONS CURRENTLY IN
FORCE IN THE COUNTRY IN WHICH THE MACHINE IS TO BE INSTALLED AND MUST BE APPROVED
BY A COMPETENT TECHNICIAN.
IN COUNTRIES WHERE THERE ARE NO REGULATIONS GOVERNING THE VENTILATION OF PREMISES
WITH GAS HEATING, THE VENTILATION CONDITIONS SET FORTH IN SECTIONS 3.6.1 and 3.6.2 ARE
RECOMMENDED.
THIS DRYER MUST NOT BE INSTALLED IN PREMISES WITHOUT ADEQUATE VENTILATION.
INADEQUATELY VENTILATED PREMISES CAN SERIOUSLY AFFECT PEOPLE'S HEALTH.
ALWAYS KEEP THE VENTILATION SYSTEM CLEAR.
NEVER PLACE OBJECTS IN PLACES WHERE THEY CAN OBSTRUCT THE PREMISE'S VENTILATION
OPENINGS.
In there are various forced draught or convection boilers/machines in the same premises, the complete cross-
section of the opening to the outside must amount to at least the sum of the ventilation cross-sections for each
piece of equipment.
To avoid the presence of crossed air currents never install equipment with convection ventilation between
forced exhaust equipment and the ventilation openings.

3.6.1. Minimum ventilation openings. Machines with electric heating

To replace the air used by the extraction, the premises must
be sufficiently ventilated. (Fig. 3.6).
Refer to extraction flow (B).
EV value in Chapter 4: Technical and connection details
for the machine.
Minimum ventilation openings (A) (data for illustrative
purposes).
Models ED260 and ED340: 0.07 m² (105 sq.in)
Models ED460 and ED660: 0.15 m² (225 sq.in)
Models ED900 and ED1250: 0.30 m² (450 sq.in)
Minimum ventilation openings (A) protected by a deflecting
grill (data for illustrative purposes).
Models ED260 and ED340: 0.1 m² (150 sq.in)
Models ED460 and ED660: 0.2 m² (300 sq.in)
Models ED900 and ED1250: 0.40 m² (600 sq.in)
In the case of rectangular air openings, the longest side must
not be more than double the length of the smaller side.
This opening must be located close to the dryer and near the
floor.
The ventilation air openings must not come into contact with
the possible air cavities in the walls.
Location
25
Fig. 3.6
Code No. 549758
Rev. nº 10/0418