Prong
Function
1
Positive terminal (+), 10-40 VDC power supply.
2
RS485 / +.
3
Common power supply (ground).
4
RS485 / -.
5
Unused.
Wireless OLCT 80 transmitter
Figure 47: wireless OLCT 80 connections.
Item
Description
B.
Auxiliary input #1, 4-20 mA, 24 VDC.
C.
Auxiliary input #2, 4-20 mA, 24 VDC.
Fault relay output. Dry contact. Interrupting capacity: 30 VDC - 250 VAC – 2A.
D.
Alarm #2 relay output. Dry contact. Interrupting capacity: 30 VDC - 250 VAC – 2A.
E.
Alarm #1 relay output. Dry contact. Interrupting capacity: 30 VDC - 250 VAC – 2A.
F.
J.
24 VDC power supply.

Configuration

This procedure must be performed in a workshop, i.e., a non-
hazardous area.
The data transmission speed of the Modbus serial connection is 9600 bauds,
no parity.
Modifying the microswitches
In a mesh network, the OLCT 80's wireless cards must be configured in
repeater mode. Follow the steps below:
Cut off power to the OLCT 80 before modifying the position of the
microswitches.
Position the microswitches as shown below (Figure 48, A) on the wireless
card of each OLCT 80:
Wire color
Brown
White
Blue
Black
Gray
5 – Wireless Version
63