Chgt Sens - Oldham OLCT 80 User Manual

Gas transmitter
Hide thumbs Also See for OLCT 80:
Table of Contents

Advertisement

Chgt sens

This procedure must be carried out after the main sensor is replaced. This
menu resets the wear rate value for the main sensor, which is displayed under
the Maintenance menu (see T. usure % on page 42). The zeroing and
sensitivity adjustment procedure must be carried out for the new sensor (see
Sensor calibration on page 45).
How to access
See Figure 31.
Tree structure
Figure 33: the Sensor Replacement menu. Press ESC repeatedly to return to the
reading display.
Menu
Description
Chgt sens.?
Confirm that you want to begin the wear rate reset procedure for the
main sensor.
Init sens ?
ENTER: reset the wear rate value for the main sensor and return
to the CALIBRA menu.
ESC: cancel the reset of the wear rate value for the main sensor
and return to the CALIBRA menu.
3 – Menus
47