PG SERIE

Purpose
Configure the serial connection and the backlighting of the LCD display.
How to access
See Figure 20.
Tree structure
Menu
Description
Ascii
Define the data transmission format:
Ascii: data are transmitted in 7-bit format; a byte thus contains the
code for 2 characters. Threads are coded in hexadecimal format.
Binary: data are transmitted in 8-bit format; a byte thus contains
the code for 1 character.
Slave Sens
Define the slave number of the main sensor (value between 1 and
255). The number 0 indicates that all of the slaves are affected;
therefore, it is best to avoid using this value.
Slave ANA1
Define the slave number of the ANA1 sensor (value between 1 and
255).
Slave ANA2
Define the slave number of the ANA2 sensor (value between 1 and
255).
Slave Rel.
Define the slave number of each of the 3 alarm relays (value
between 1 and 255).
38400 Baud
Define the data transmission speed. The pre-defined speeds are
1200, 2400, 4800, 9600, 19200 and 38400 bauds.
LINE
Line: used if the OLCT 80 is connected to the line of an MX 43.
Loop: used if the OLCT 80 is connected to the loop of an MX 62
or an API, for example.
Back ON
Yes: the display is always backlit.
No: the display illuminates once a button is pressed on the IR 20
remote control.
Sûre ??
ENTER: confirm the changes made and return to the PROG
menu.
ESC: cancel the changes made and return to the PROG menu.
Communication with an MX 43 central controller: configure
binary mode at 9600 bauds.
Communication with an MX62 central controller: configure
ASCII mode at 38400 bauds.