Before connecting the detector to the control unit, please inhibit any installation
alarms to avoid unexpected triggering during operation.
The connection of the cable between the detector and central unit should be
made with the power off. The site should be at equal potential
Connecting is made according to the following schematic:
Ground
Terminal
Figure 3 : principle of connecting modules on a MX43 line.

Configuration of communication

Detector address
All the digital modules on a line must be
identified by a unique address.
Switches 1 to 5 of the configuration block of
each module make it possible to establish
an address number (1 to 32) in binary
mode.
In the illustration to the right, the address 9
(10010) has been defined.
The Addressing Table below lists the
possible combinations.
OLCT10N
10
Manual
MX43 line terminal
Detector terminal
Figure
4 :
Switches
address configuration.
*
004