Configuring the auxiliary inputs to connect a 3-wire
4-20mA sensor
In 1 input used: apply a solder joint to PPS2 and PPS7, remove PPS1.
In 2 input used: apply a solder joint to PPS4 and PPS8, remove PPS3.
Figure 62: auxiliary input configuration for a 3-wire 4-20mA sensor.
Configuring the auxiliary inputs to connect a 4-wire
4-20mA sensor
In 1 input used: apply a solder joint to PPS1 and PPS7, remove PPS2.
In 2 input used: apply a solder joint to PPS3 and PPS8, remove PPS4.
Figure 63: auxiliary input configuration for a 4-wire 4-20mA sensor.
.
7 – Pre-installation Hardware Configuration
75