3. Diagnosis
3.2
Testing the valves
Test routine
Festo P.BE−CP−FB11−E−EN en 0802d
Warning
Before the test:
S Switch off the compressed air supply for the valves.
S In the case of a non−saved string assignment:
Save the existing string assignment.
You can thereby avoid:
undesired or dangerous movements of the actuators
repeated actuation of the SAVE button.
Caution
This test function runs automatically in the CP terminals.
All the valves are switched on/off cyclically.
None of the programmed lockings or further switching
conditions will be taken into account.
During the test routine of the CP valve terminal, all the valves
will be switched on and off at 1−second intervals.
3−9