Operate
6.2 Parameter description
"2.4.2.3 Zero Trim"
Purpose:
Description:
"2.4.2.4 Reset Zero- and Sensortrim"
Purpose:
Description:
"2.4.2.5 DA-Converter"
Purpose:
Description:
"2.4.3 Trim"
"2.4.3.1 DA-Converter"
"2.4.3.1.1 4 mA"
Purpose:
Description:
106
Resetting the position error correction
The parameter resets position error correction to factory state.
See also
Zero point calibration (position correction) (Page 160)
Resetting the zero calibration and sensor calibration
The parameter resets zero and sensor calibration to factory state.
See also
Trimming the sensor (Page 161)
Resetting the current calibration
The parameter resets the current calibration to factory state.
See also
Current simulator trim (Page 162)
"2.4.3.1 DA-Converter" (Page 106)
Digital analog converter calibration at 4 mA
Trimming is carried out in 3 steps:
"2.4.3.1.1.1 Enable 4 mA fixed"
•
This menu command causes the pressure transmitter to output 4 mA
constant current.
"2.4.3.1.1.2 enter value"
•
This reads the indicated current value on a connected ammeter, and en-
ters it in the menu.
"2.4.3.1.1.3 perform zero-point calibration"
•
The pressure transmitter performs a calibration and uses this value to
correct the current offset.
SITRANS P500 with HART
Operating Instructions, 12/2014, A5E02344528-09