Measuring Mode "Volume - Siemens Sitrans P500 Operating Instructions Manual

Pressure transmitter
Table of Contents

Advertisement

Example
In the following calculation example these sensor limits are taken as 0 and 4 bar. You can
also set up a down-scaling; e.g. 1:2. A down-scaling of 1:2 corresponds to 50 % of the
nominal measuring range, i.e. in this case 2 bar.
MA
ME
p
Figure 6-7
For the output scaling of "level", specify the measuring range limits with a unit from the level
range. Parameters may be assigned, for instance, at 10 and 20 m. This means that at a
process pressure of 0 bar, "level" is shown as 10 m and at 2 bar it is shown as 20 m.
See also
"2.1.6 Level" (Page 94)
6.3.2.4

Measuring mode "Volume"

Description
If parameters are assigned to the measuring mode "Volume", the geometry of the vessel can
be reflected in the level characteristic.
SITRANS P500 with HART
Operating Instructions, 12/2014, A5E02344528-09
Start of scale value
Full scale value
Pressure
Calculation of level, volume and mass
6.3 Description of the operating functions
L
Level
V
Volume
m
Mass
Operate
147