6.2 Parameter description
Purpose:
Description:
"4.22.2 Burst Command"
Factory setting:
Setting range:
Purpose:
Description:
"4.22.3 .. 4.22.6 Burstvariable 4"
In this sub-menu you can select the parameter to be transmitted in burst mode. However,
you can only select parameters which are active.
Men item
4.23.3
4.23.4
4.23.5
4.23.6
6.2.6

"5 Security"

6.2.6.1

"5.1 " in preparation

6.2.6.2

"5.2 Keypad Lock"

"5.2.1 Enable"
Purpose:
Description:
140
Activate/ deactivate burst mode
This parameter activates burst mode. Activating burst mode causes the
current output to be set to a constant 4 mA; it no longer responds to the
measured signal.
Read PV
Read PV
Read current in [mA] and PV in [%]
Read dynamic variables and current
Read device variables and status
Select the information to be transmitted in burst mode
This parameter allows you to select which information from the selected
measured value should be transmitted in burst mode.
Designation
Burstvariable 1
Burstvariable 2
Burstvariable 3
Burstvariable 4
Activate the key lock
Only those parameters that are set to "5.2.2 Setting" (Page 141)"On" are
visible.
This parameter locks the local operation keyboard.
The key lock can be released by depressing the "right key" for longer than
2 seconds.
SITRANS P500 with HART
Operating Instructions, 12/2014, A5E02344528-09