A.2.5 Process temperature limits
Table A-4. Gage/Absolute Sensor
Configuration
Silicone fill fluid
with coplanar flange
with traditional flange
with level flange
with Rosemount 305 Integral Manifold
(3)
Inert fill fluid
1.
Process temperatures above 185 °F (85 °C) require derating the ambient limits by a 1.5:1 ratio. For example, for process temperature of 195 °F (91 °C), new ambient
temperature limit is equal to 170 °F (77 °C). This can be determined as follows: (195 °F - 185 °F)3 1.5 = 15 °F, 185 °F - 15 °F = 170 °F.
2.
220 °F (104 °C) limit in vacuum service; 130 °F (54 °C) for pressures below 0.5 psia.
3.
Not available with Rosemount 3051SAM_ _A.
4.
160 °F (71 °C) limit in vacuum service.
Table A-5. Liquid Level Sensor (Rosemount 3051SAL)
Fill fluid
200 Silicone
®
Dow Corning
Silicone 704 Diffusion
Pump Fluid
Inert (Halocarbon)
SYLTHERM
XLT
Silicone
Glycerin and water
Propylene Glycol and
water
®
Neobee
M-20
Figure A-1
1.
See
for the specific operating range of using the Thermal Optimizer withD.C. Silicone 704.
70
Coplanar gage/absolute sensor
(Rosemount 3051SAM_ _G, Rosemount
–40 to 250 °F (–40 to 121 °C)
–40 to 300 °F (–40 to 149 °C)
–40 to 300 °F (–40 to 149 °C)
–40 to 300 °F (–40 to 149 °C)
–40 to 185 °F (–40 to 85 °C)
Process temperature limits at 70 °F (21 °C) ambient and atmospheric pressure or above
No extension
2-in. (50 mm) extension 4-in. (100 mm) extension
–49 to 401 °F
(–45 to 205 °C)
32 to 401 °F
(0 to 205 °C)
–49 to 320 °F
(–45 to 160 °C)
–102 to 293 °F
(–75 to 145 °C)
5 to 203 °F
(-15 to 95 °C)
5 to 203 °F
(-15 to 95 °C)
5 to 401 °F
(-15 to 205 °C)
3051SAM_ _A)
N/A
(1)(2)
(1)(2)
(1)(2)
(1)(2)
(4)
–49 to 401 °F
(–45 to 205 °C)
32 to 464 °F
(0 to 240 °C)
–49 to 320 °F
(–45 to 160 °C)
–102 to 293 °F
(–75 to 145 °C)
5 to 203 °F
(–15 to 95 °C)
5 to 203 °F
(–15 to 95 °C)
5 to 437 °F
(–15 to 225 °C)
Specifications and Reference Data
In-Line gage sensor/absolute sensor
(Rosemount 3051SAM_ _T, Rosemount
3051SAM_ _E)
–40 to 250 °F (–40 to 121 °C)
N/A
N/A
N/A
N/A
–22 to 250 °F (–30 to 121 °C)
Thermal optimizer
–49 to 401 °F
(–45 to 205 °C)
32 to 500 °F
(0 to 260 °C)
–49 to 320 °F
(–45 to 160 °C)
–102 to 293 °F
(–75 to 145 °C)
5 to 203 °F
(–15 to 95 °C)
5 to 203 °F
(–15 to 95 °C)
5 to 437 °F
(–15 to 225 °C)
Specifications and Reference Data
November 2016
(1)(2)
(1)(2)
(1)
–49 to 401 °F
(–45 to 205 °C)
32 to 599 °F
(0 to 315 °C)
–49 to 320 °F
(–45 to 160 °C)
–102 to 293 °F
(–75 to 145 °C)
5 to 203 °F
(–15 to 95 °C)
5 to 203 °F
(–15 to 95 °C)
5 to 437 °F
(–15 to 225 °C)