Product Certifications
November 2016
Parameters
Voltage U
i
Current I
i
Power P
i
Capacitance C
i
Inductance L
i
Special Conditions for Safe Use (X):
1. The Rosemount 3051S Transmitters fitted with transient
protection are not capable of withstanding the 500V test as
defined in Clause 6.3.13 of EN 60079-11:2012. This must be
taken into account during installation.
2. The terminal pins of the Rosemount 3051S SuperModule
must be provided with a degree of protection of at least IP20
in accordance with IEC/EN 60529.
3. The Rosemount 3051S enclosure may be made of aluminum
alloy and given a protective polyurethane paint finish;
however, care should be taken to protect it from impact or
abrasion if located in a zone 0 area.
ND ATEX Dust
Certificate: BAS01ATEX1374X
Standards: EN 60079-0: 2012, EN 60079-31: 2009
Markings:
II 1 D Ex ta IIIC T105 °C T
Ta
+85 °C), V
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress
protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking
plugs which maintain the ingress protection of the enclosure
to at least IP66.
3. Cable entries and blanking plugs must be suitable for the
ambient temperature range of the apparatus and capable of
withstanding a 7J impact test.
4. The SuperModule(s) must be securely screwed in place to
maintain the ingress protection of the enclosure(s).
N1
ATEX Type n
Certificate: BAS01ATEX3304X
Standards: EN 60079-0: 2012, EN 60079-15: 2010
Markings:
II 3G Ex nA IIC T5 Gc, (–40 °C
= 45V
Special Condition for Safe Use (X):
1. The equipment is not capable of withstanding the 500V
insulation test required by clause 6.5 of EN 60079-15:2010.
This must be taken into account when installing the
equipment.
Note
RTD Assembly is not included with the 3051SFx Type n Approval.
Product Certifications
FISCO
17.5 V
380 mA
5.32 W
0
0
95 °C Da, (–20 °C
500
= 42.4 V
max
Ta
+85 °C), V
B.7 International
E7
IECEx Flameproof and Dust
Certificate: IECEx KEM 08.0010X (Flameproof)
Standards: IEC 60079-0:2011, IEC 60079-1: 2007, IEC
60079-26:2006 (3051SFx models with RTD are
certified to IEC 60079-0:2004)
Markings: Ex d IIC T6...T4 Ga/Gb, T6(–60 °C
T5/T4(–60 °C
Temperature class
T6
T5
T4
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation,
maintenance and use shall take into account the
environmental conditions to which the diaphragm will be
subjected. The manufacturer's instructions for installation
and maintenance shall be followed in detail to assure safety
during its expected lifetime.
2. For information on the dimensions of the flameproof joints
the manufacturer shall be contacted.
Certificate: IECEx BAS 09.0014X (Dust)
Standards: IEC 60079-0:2011, IEC 60079-31:2008
Markings: Ex ta IIIC T105 °C T
+85 °C), V
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress
protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking
plugs which maintain the ingress protection of the enclosure
to at least IP66.
3. Cable entries and blanking plugs must be suitable for the
ambient temperature range of the apparatus and capable of
withstanding a 7J impact test.
4. The 3051S- SuperModule must be securely screwed in place
to maintain the ingress protection of the enclosure.
I7
IECEx Intrinsic Safety
Certificate: IECEx BAS 04.0017X
max
Standards: IEC 60079-0: 2011, IEC 60079-11: 2011
Markings: Ex ia IIC T4 Ga, T4(–60 °C
Reference Manual
00809-0100-4804, Rev CB
Ta
Ta
+80 °C)
Process temperature
–60 °C to +70 °C
–60 °C to +80 °C
–60 °C to +120 °C
95 °C Da, (–20 °C
500
= 42.4 V
max
Ta
+70 °C)
+70 °C),
Ta
115