Process Alerts - Emerson Rosemount 3051S ERS Reference Manual

Electronic remote sensor system
Hide thumbs Also See for Rosemount 3051S ERS:
Table of Contents

Advertisement

Configuration
November 2016
3.5.6

Process alerts

Fast Keys
Process alerts allow for the configuration of the ERS System to output a HART message when a
parameter (such as the measured DP) exceeds a user-defined operating window. An alert will be
communicated to the HART host (such as a Field Communicator or AMS Device Manager) when polled,
and on the LCD display of the ERS System. The alert will reset once the value returns within range.
Process alerts may be configured for the following parameters:
Differential pressure
P
HI
P
LO
P
HI
P
LO
Configure process alerts
1. Select a parameter for which the process alert will be configured.
2. Set the Alert Mode to "enable."
3. Define the low alert value. If the measured value for the parameter goes below the low alert value, an
alert message will be generated.
4. Define the high alert value. if the measured value for the parameter goes above the high alert value,
an alert message will be generated.
Disable process alerts
1. Select a parameter for which the process alert will be disabled.
2. Set the Alert Mode to "disabled."
38
2, 3
pressure
pressure
module temperature
module temperature
Reference Manual
00809-0100-4804, Rev CB
Configuration