Occupancy Sensor
Step 5:
Step 6:

Soft Ceiling Tile Installation

Step 1:
Step 2:
Step 3:
Occupancy Sensor Installation Guide
Strip each wire 5/16" (8mm) and terminate the white, black,
and green (ground) wires to the terminal block located on the
sensor control board. Torque each termination
to 3.1-3.5 in-lb.
a: Terminate the white incoming wire to terminal A.
b: Terminate the black incoming wire to terminal B.
c: Terminate the green wire to the ground terminal.
Attach the sensor to the mounting plate by aligning the tabs on
the sensor with the slots on the mounting plate, then twist
clockwise until the two are locked into place.
poke the adapter through the ceiling tile, then bend
it over for a secure fit.
Pull the Belden 8471 (or equivalent) and 14 AWG (2.5mm
ground wire to the installation location.
Orient the smooth side of the mounting plate to the ceiling tile
and insert the soft ceiling tile adapter through the two small
holes near the center of the mounting plate.
Poke the adapter tines through the ceiling tile, then bend each
tine over in opposite directions for a secure fit.
Page 4 of 8
LinkConnect pigtail and
WAGO connectors
(optional use)
terminate
wires here