Occupancy Sensor Installation Guide
Prepare the site for configuration.
a: Make certain the sensor and lighting loads are powered
and connected for control by the Paradigm control
system.
b: You will need direct access to the Paradigm Occupancy
Sensor in order to place it into walk test mode.
Alternatively, you can invoke the walk test mode by
sending a Wink command from the connected Paradigm
control system. Reference the LightDesigner Online Help
System for instructions to send a Wink command.
The sensor must be connected and bound to the Paradigm
Architectural Control Processor (P-ACP) in order to enable Walk
Test Mode.
See "Binding Sensors to Paradigm" on page 6.
Press the [Walk Test] button on
the front of the sensor to enable
the walk test feature at the
sensor. A green LED will begin to
flash, indicating the walk test is
enabled and the vacancy / no
vacancy occupancy timer will be
shortened to 10 seconds.
Move throughout the space
including corners and areas that
may specifically be obscured
from line of sight to the sensor. Each time the sensor detects
movement, the lens will illuminate red.
Adjust the lens masking, if installed, blocking certain areas of
the installed space from sensor detection. See
page
5.
Walk test mode will automatically exit after five minutes from
the time it was enabled. To manually exit the walk test mode,
press either of the buttons on the sensor.
Page 7 of 8
service
service
button
button
Lens Masking
Electronic Theatre Controls, Inc.
walk test
walk test
button
button