Lens Masking - ETC P-OCC-SR Installation Manual

Unison paradigm
Table of Contents

Advertisement

ETC Installation Guide
Occupancy Sensor
Step 4:
Step 5:
Step 6:
Step 7:

Lens Masking

Lens masks are provided in the packaging for your convenience.
Occupancy Sensor Installation Guide
If you are installing the sensor in series with other sensors
or stations (continuing the data run), use the provided
LinkConnect pigtail, ESD ground wire pigtail and WAGO
connectors to make the terminations. If you are not
continuing the data run, proceed to step 5.
a: Strip 3/16" (5mm) of insulation from each installed wire.
b: Open the three terminal levers on a WAGO connector
and insert the installed (typically black) Belden 8471
LinkConnect wire, the black lead from the sensor pigtail,
and the continuing Belden 8471 (typically black) wire into
the terminals.
c: Close the levers onto the wires.
d: Repeat the above for the installed (typically white) Belden
8471 LinkConnect wire and the remaining pigtail from
the sensor, as well as the ESD ground wires using a new
WAGO connector for each termination type.
Create a hole for wire pass-through in the ceiling tile by poking
through the center hole or oblong hole of the mounting plate,
then pull the wires through.
Strip each wire 5/16" (8mm) and terminate the white, black,
and green (ground) wires to the LON terminal block located on
the sensor control board. Torque each termination
to 3.1-3.5 in-lb.
a: Terminate the white incoming wire to terminal A.
b: Terminate the black incoming wire to terminal B.
c: Terminate the green wire to the labeled ground terminal.
Attach the sensor to the mounting plate by aligning the tabs on
the sensor with the slots on the mounting plate, then twist
clockwise until the two are locked into place.
Step 1:
Step 2:
Step 3:
Page 5 of 8
As needed, trim the lens mask to fit
the desired area to be blocked.
Gently press down on the sensor
lens, which will give only slightly,
and insert the lens mask.
Rotate the lens mask around the
dome to block the required area
from occupancy sensing.
Electronic Theatre Controls, Inc.