Motor data for parameterization

Figure 3-7
NOTICE
P0308 & P0309 are only visible if P0003 ≥ 2. Only one of the parameters is
shown depending on the settings of P0100.
Changing motor parameters is not possible unless P0010 = 1(factory setting)
and P0004 = 0 or 3.
Ensure that the inverter is configured correctly to the motor.
3.3.4.4

Reset to Factory default

To reset all parameters to the factory default settings; the following parameters
should be set as follows:
1. Set P0010 = 30
2. Set P0970 = 1
NOTICE
1. The reset process can take up to 3 minutes to complete.
2. Refer to Parameter P0399 for description on saving motor data sets while
performing a reset to the factory defaults.
MICROMASTER 411 & COMBIMASTER 411
6SE6400-5CA00-0BP0
Typical Motor Rating Plate Example
Operating Instructions
3 Commissioning
55