Fuses And Circuit Breakers; Table 7-6 Micromaster 411/Combimaster 411 Fuses And Circuit Breakers - Siemens MICROMASTER 411 Operating Instructions Manual

Siemens welding system - ac/dc welding inverter user manual
Hide thumbs Also See for MICROMASTER 411:
Table of Contents

Advertisement

Issue 03/01
7.5

Fuses and Circuit Breakers

Table 7-6
MICRO MICROMASTER 411
COMBIMASTER 411
(without filter)
380 V to 480 V 3 AC
MICROMASTER 411
COMBIMASTER 411
(with Class B filter)
380 V to 480 V 3 AC
MICROMASTER 411 & COMBIMASTER 411
6SE6400-5CA00-0BP0
MICROMASTER 411/COMBIMASTER 411 Fuses and Circuit Breakers
Power
Inverter
kW
0,37
0,55
0,75
1,1
1,5
2,2
3,0
0,37
0,55
0,75
1,1
1,5
2,2
3,0
Operating Instructions
Case Size
Fuses
Hp
0,5
B
3NA3803
0,75
B
3NA3803
1,0
B
3NA3803
1,5
B
3NA3803
2,0
B
3NA3803
3,0
C
3NA3805
4,0
C
3NA3805
0,5
B
3NA3803
0,75
B
3NA3803
1,0
B
3NA3803
1,5
B
3NA3803
2,0
B
3NA3803
3,0
C
3NA3805
4,0
C
3NA3805
7 Specifications
Circuit Breakers
3RV1021-1CA10
3RV1021-1DA10
3RV1021-1EA10
3RV1021-1GA10
3RV1021-1HA10
3RV1021-1JA10
3RV1021-4KA10
3RV1021-1CA10
3RV1021-1DA10
3RV1021-1EA10
3RV1021-1GA10
3RV1021-1HA10
3RV1021-1JA10
3RV1021-1KA10