3 Commissioning
Flow chart Quick Commissioning (Level 1 Only)
P0010
Start Quick Commissioning
0
Ready to Run
1
Quick Commissioning
30 Factory Setting
Note
P0010 must always be set back to '0' before
operating the motor. However if P3900 = 1 is set
after commissioning this is done automatically.
P0100 Operation for Europe/N. America
0
Power in kW; f default 50 Hz
1
Power in hp; f default 60 Hz
2
Power in kW; f default 60 Hz
Note
Settings 0 & 1 can be changed using the 60Hz
Jumper to allow permanent setting.
P0304 Rated Motor Voltage 1)
10 V - 2000 V
Nominal motor voltage (V) from rating plate
P0305 Rated Motor Current 1)
0 - 2 x inverter rated current (A)
Nominal motor current (A) from rating plate
P0307 Rated Motor Power 1)
0 kW - 2000 kW
Nominal motor power (kW) from rating plate.
If P0100 = 1, values will be in hp
P0310 Rated Motor Frequency 1)
12 Hz - 650 Hz
Nominal motor frequency (Hz) from rating plate
P0311 Rated Motor Speed 1)
0 - 40000 1/min
Nominal motor speed (rpm) from rating plate
1) related parameters – please refer to motor rating plate drawing.
2) Denotes parameters that contain more detailed lists of possible settings for use in specific
applications. Please refer to the Parameter List.
54
P0700 Selection of Command Source 2)
(on / off / reverse)
0
Factory Setting
1
Basic Operator Panel
2
Terminal / Digital Inputs (Default)
P1000 Selection of Frequency Setpoint 2)
0
No frequency setpoint
1. BOP frequency control
2. Analogue Setpoint
27.
Setpoint Addition: Analogue Setpoint &
Control Potentiometer(Default)
P1080 Min. Motor Frequency
Sets minimum motor frequency (0-650Hz) at which
the motor will run irrespective of the frequency
setpoint. The value set here is valid for both
clockwise and anti-clockwise rotation.
P1082 Max. Motor Frequency
Sets maximum motor frequency (0-650Hz) at which
the motor will run at irrespective of the frequency
setpoint. The value set here is valid for both
clockwise and anti-clockwise rotation.
P1120 Ramp-Up Time
0 s - 650 s
Time taken for the motor to accelerate from
standstill up to maximum motor frequency.
P1121 Ramp-Down Time
0 s - 650 s
Time taken for motor to decelerate from maximum
motor frequency down to standstill.
P3900 End Quick Commissioning
0
No Quick Commissioning.
1
Perform Quick Commissioning with factory reset
of all other Parameters (Recommended).
MICROMASTER 411 & COMBIMASTER 411
Issue 03/01
Operating Instructions
6SE6400-5CA00-0BP0