Command Sources (P0700); Off And Braking Functions - Siemens MICROMASTER 411 Operating Instructions Manual

Siemens welding system - ac/dc welding inverter user manual
Hide thumbs Also See for MICROMASTER 411:
Table of Contents

Advertisement

Issue 03/01
4.2

Command Sources (P0700)

NOTICE
The ramp times and ramp-smoothing functions also affect how the motor starts
and stops. For details of these functions, please refer to parameters P1120, P1121,
P1130 – P1134 in the Parameter List.
Starting the motor
Default
Other Settings
Stopping the motor
There are several ways to stop the motor:
Default:
OFF1 (4.3.1)
OFF2 (4.3.2)
OFF3 (4.3.3)
Other Settings
Reversing the motor
Default
Other Settings
4.3

OFF and Braking Functions

4.3.1
OFF1
This command (produced by canceling the ON command) causes the inverter to
come to a standstill at the selected ramp-down rate.
Parameter to change ramp time see P1121
NOTICE
ON and the following OFF1 command must have the same source.
If the ON/OFF1 Command is set to more than one Digital input, only the last
set Digital Input is active e.g. DIN3 active.
OFF1 can be combined with DC braking or Compound braking.
MICROMASTER 411 & COMBIMASTER 411
6SE6400-5CA00-0BP0
4 Using the MICROMASTER 411 / COMBIMASTER 411
Terminal 1 (DIN 1): (P0700=2)
see P0700 to P0704
Terminal 1 (DIN 1): (P0700=2)
Off button on BOP/AOP. Pressing the Off button once
(two seconds) or twice (with default settings). This is not
possible without BOP/AOP
no standard setting
see P0700 to P0704
Terminal 2 (DIN 2)
see P0700 to P0704
Operating Instructions
63

Advertisement

Table of Contents
loading

This manual is also suitable for:

Combimaster 411

Table of Contents