3 Commissioning
3.4.3
Non - Default Modes of Operation
Non-default modes of operation require the use of either a Keypad (BOP or AOP)
or a Commissioning tool (Drive Monitor or Starter) in order to change from the
default parameter settings.
The BOP, Part Number: 6SE6400-0BP00-0AA0 is housed in an Operator Panel
Mounting Kit, Part Number 6SE6401-1DF00-0AA0 and connected via the Interface
Link Cable, Part Number 6SE6401-1BL00-0AA0 to the Inverter serial comms port.
This arrangement is shown in Figure 3-9.
Figure 3-9
Prerequisites
P0010 = 0 (in order to initiate the run command correctly).
P0700 = 1 (enables the start/stop button on the BOP).
P1000 = 1 (this enables the motor potentiometer setpoints).
1. Press the green Button
2. Press the Button
50 Hz.
3. When the inverter reaches 50 Hz, press the Button
display is decreased.
4. Change the direction of rotation with the Button
5. The red button stops the motor
58
Connect BOP/AOP with the MICROMASTER 411
to start the motor.
while the motor is turning. Motor speed increases to
MICROMASTER 411 & COMBIMASTER 411
. Motor speed and
.
.
Issue 03/01
Operating Instructions
6SE6400-5CA00-0BP0