DSC TL280 Installation Manual page 19

Internet alarm communicator - international
Hide thumbs Also See for TL280:
Table of Contents

Advertisement

This section may be used by the installer to force the communicator to send an immediate test transmission to specific receivers,
to verify that the communications paths are available. Diagnostic test transmission failure will indicate as FTC trouble (yellow
LED = 9 flashes). If an FTC error occurs when testing all receivers, select only one receiver and repeat test to isolate the
receiver that is not communicating.
NOTE: Sending a test transmission to a receiver that is not programmed generates FTC trouble.
System Information (Read Only)
NOTE: Sections [983] - [998] are provided for information (read only). Values in these sections cannot be modified by the
installer.
[983] Firmware Update Diagnostics Section
Firmware updates for panel and the communicator itself can be made from the communicator.
The firmware update diagnostic section is a read only 2-digit, hexadecimal section.
l
Response
Description of Response Code
Code
Bad File
00
Version check failed
01
Image type mismatch
02
Device type mismatch
03
Hardware type mismatch
04
General variant mismatch
05
Firmware header wrong length
Panel is Busy
20
System update pending - panel is armed
System update pending -AC trouble (Any
21
AC trouble; device/module)
System update pending -low battery (Any
22
low battery trouble; device/module)
System update pending - communication in
25
progress
Firmware Update Sequence Change
A0
System firmware update successful
A1
System firmware update failure
System firmware update failure - module not
A2
found
AA
Device firmware transfer begin
AB
Device firmware module update begin
AC
General device firmware transfer failure
Firmware Update Status
C0
System ready to update.
C1
System update cancel request received
C2
System update begin
Firmware Download Request Reject
Table 11: Response Code Descriptions and Corresponding Actions
Corresponding Action
Contact DSC Tech Support, described the action attempted with
the system and supply them with the Response Code in Section
[983].
Disarm the panel to continue with system firmware update
process.
Resolve the AC trouble to continue with system firmware update
process.
Resolve the low battery trouble to continue with system firmware
update process.
Retry in a few minutes; if issue persists, contact DSC Tech
Support.
None
At least one module was not updated. Use DLS to reapply the
firmware to the module not updated.
At least one module was not responding during firmware
update. Ensure all modules enrolled are physically connected
and powered up.
None
None
Contact DSC Tech Support, describe the action attempted with
the system and supply them with the Response Code in Section
[983].
None
The system has received an update cancel request from DLS.
None