Communications Reporting Codes
Event
[023] Panel Absent Trouble
[024] Panel Absent Trouble Restore
[026] Ethernet 1 Test Transmission
[027] Ethernet 2 Test Transmission
[030] FTC Restore
[023] Panel Absent Trouble
Default (FF)
Program 00 to disable this event or FF to enable. This event will occur when communications with the panel have been lost for
more than 60 seconds.
[024] Panel Absent Trouble Restore
Default (FF)
Program 00 to disable this event or FF to enable. This event will occur when communications with the control panel have
resumed.
System Test Options
Test Transmissions to Primary Receiver, with Backup to Secondary Receiver:
Set Ethernet section [026] to (FF); [027] to (00).
If the test transmission fails to the primary receiver it will backup to the secondary receiver.
l
If the test transmission fails to the secondary receiver an FTC trouble will be generated.
l
Independent Test Transmission to Primary and Secondary Receivers:
Set Ethernet section [026] to (FF); [027] to (FF).
The module will send periodic test transmissions to each receiver independently, with no backups.
l
If the test transmission fails to any of the programmed receivers, an FTC trouble will be generated.
l
Alternating Test Transmission:
Alternate test transmission can be enabled or disabled in section [005] toggle option [7].
Alternating Test Transmission with backup receivers:
Set Ethernet section [026] to (FF); [027] to (00).
Interval 1:
If the test transmission fails to the primary receiver it will backup to the secondary receiver.
l
If the test transmission fails to the secondary receiver an FTC trouble will be generated.
l
Interval 2:
If the test transmission fails to the secondary receiver it will backup to the primary receiver.
l
If the test transmission fails to the primary receiver an FTC trouble will be generated.
l
Test Transmission Unique to Primary and Secondary Receivers:
Set Ethernet section [026] to (FF); [027] to (FF).
Interval 1:
The module will send periodic test transmissions to primary receivers (Ethernet primary) independently, with no backups.
l
If the test transmission fails to any of the programmed primary receivers, an FTC trouble will be generated.
l
Interval 2:
The module will send periodic test transmissions to secondary receivers (Ethernet secondary) independently, with no
l
backups.
If the test transmission fails to any of the programmed secondary receivers, an FTC trouble will be generated.
l
[026] Ethernet 1 Transmission
Default (FF)
Program 00 to disable this event transmission or FF to enable. See system test options (above) for details on settings.
[027] Ethernet 2 Transmission
Default (00)
Program 00 to disable this event transmission or FF to enable. See system test options (above) for details on settings.
Table 8: Communications Reporting Codes
SIA
SIA
Identifier
ReportingCode
ET
0001
ER
0001
RP
0001
RP
0002
YK
0001
15
CID
CID
CID
Event
Reporting
Qualifier
Code
Code
1
3
55
3
3
55
1
6
A3
1
6
A3
3
3
54
CID
User/Zone
001
001
951
952
001

Advertisement