AS20WRF/BRF Thermostat – Functions & Parameters
Function
d00
Select Units
d01
Heating Control
d02
Temp . Offset
d03
Outdoor Sensor
d04
External Sensor
d05
Cooling Control
d06
Actuator Type
d07
Valve Protection
d08
Frost Setpoint
41ºF (5 .0ºC)
d09
Hour Format
d10
Not Applicable
d11
Daylight Savings
Max . Heat
d12
95ºF (35ºC)
Setpoint
d13
Max . Cool Setpoint
Floor Sensor High
d14
81°F (27°C)
Limit (heating)
Floor Sensor Low
d15
50°F (10°C)
Limit (heating)
Floor Sensor Low
d16
Limit (cooling)
d17
Preset Programs
Heat/Cool Mode
d18
Selection
Setting Device Parameters
Parameters
Default
Value
0
0
1
0
0
1
2
-6ºF to +6ºF
0
(-3 .0ºC to +3 .0ºC )
0
0
1
3
0
0
1
1
2
2
0
1
1
0
1
1
41ºF to 63ºF
(5 .0ºC -to 17ºC )
0
1
1
N/A
N/A
0
1
1
42ºF to 95ºF
(17 .5ºC to 35 .0ºC)
41ºF to 104ºF
41ºF (5ºC)
(5 .0ºC to 40 .0ºC)
59ºF to 113ºF
(15 .0ºC to 45 .0ºC)
43ºF to 104ºF
(6 .0ºC to 40 .0ºC)
43ºF to 113ºF
43°F (6°C)
(6 .0ºC to 45 .0ºC)
1
0-1
0
0
1
SI Metric Units - °C
US Customary Units - °F
Time Proportional & Integral (TPI)
ON/OFF – 0 .5°C (1 .0°F) Increments
ON/OFF – 1 .0°C (2 .0°F) increments
Room Temperature Offset (1 .0°F/0 .5°C increments)
Outdoor Sensor not connected to S1/S2
Outdoor Sensor or Ext . (d04) connected (10 kΩ)
Not Used
d03 = 1, Ext . air sensor active, Int . sensor inactive
d03 = 1, Ext . floor sensor active, Int . sensor active
ON/OFF – 1 .0°F (0 .5°C) increments
ON/OFF – 2 .0°F (1 .0°C ) increments
NO Normally Open
NC Normally Closed
ARV10RFM Valve Exercise Disable
ARV10RFM Valve Exercise Enable
Minimum room temperature for frost protection and holiday mode
12 Hour Time Format (eg . 5:00 pm)
24 Hour Time Format (eg . 17:00)
This function is not applicable
Daylight Savings Time (DST) Off
Daylight Savings Time (DST) On
Maximum setpoint for heating mode
Maximum setpoint for cooling mode
Disable heat demand when floor temperature is above high limit .
Increment: 1°F (0 .5°C)
Provide heat demand when floor temperature is below low limit .
Increment: 1°F (0 .5°C)
Disable cooling demand when floor temperature is below low limit .
Increment: 1°F (0 .5°C)
Select program . Once selected, the selected program will overwrite
the present program .
Disable Heat/Cool selection
Enable Heat/Cool selection
Description