5.3 BY-PASS OF OPEN TORQUE SWITCH WHEN STARTING TO OPEN FROM
CLOSED POSITION
In standard, the open torque switch is active on the whole actuator stroke.
Switch 6
Move switch 6 to position B to by-pass the open torque switch by the closed limit switch when
starting to open from the closed position.
This must be used when actuator including mechanically maintained torque switches [SR type] is
set for closing on torque switch. This avoid the open torque switch to trip when starting to open.
5.4 ROTATION REVERSE DELAY
In standard the reverse delay is 50ms. Jumper on support 25 in position 50ms.
Jumper 25
Move the jumper on support 25 to position 200ms to have a reverse delay of 200ms.
- Reverse delay of 200 ms
Note: the setting of the reverse delay is a factory setting. It allows the use
of bigger single phase motors.

6 REMOTE CONTROL

Remote control of an actuator equipped with the electronic board CI2701 can be done from an exter-
nal voltage supply or an internal voltage supply.
Inputs on the board are completely isolated by opto-isolators.
Pulse commands (with self-holding) requires 4 wires connected to the customer terminal board: Com-
mon, stop, open and close. If the stop button is not used, do not connect the wire STOP, open contact
(or close) must be maintained to operate the actuator.
6
- By-pass the open torque switch
by the closed limit switch in closed
position