Type of input
signal
Valve action
Configuration
10.3
'STAY PUT' FUNCTION CONFIGURATION
With input signal 4-20 mA, it is possible to configure a failsafe position in case of loss of input signal.
In standard, the function is active, and the actuator stays in position in case of loss of input signal.
Switches 5, 6 and 8
Move switch 5 to position B for actuator to ope
Move switch 6 to position B for actuator to close in case of loss of input signal.
Move switch 8 to position B to disactivate the '
Caution: in case of input signal 0-20 mA or 0-10 V, the 'stay put' function cannot be used
10.4
DEAD BAND ADJUSTMENT
This adjustment is factory done, but one can adj
To reduce the dead band turn it counter-clockw
Caution: reducing the dead band too much will provoke hunting on the actuator.
10.5
LOCAL OPERATION
One can simulate an input signal 4-20 mA locally to c
local/off/remote selector must be on the remote position.
Move local control switch to position 0%, MAN or 100%. Turn potentiometer MAN to simulate an
input signal 4-20 mA.
16
Operation direction configuration
Open
4mA
0mA
0v
Closing
clockwise
counterclockwise
CI2701 board:
switch 7 on B
Standard
Reverse
potentiometer
and must be disactivated. Move switch 8 to position B.
- AUT: Operation by external signal
- 0%: Internal signal 0% (4mA in standard)
- MAN: Internal signal adjustable from 0 to 100%
-100 %: Internal signal 100% (20mA in standard)
20mA
20mA
10V
Closing
Closing
clockwise
GAMK board:
switch 3 on B
Reverse
potentiometer
n in case of loss of input signal.
stay put' function.
ust it with the potentiometer DEAD BAND.
ise.
heck the operation of the actuator. The
Close
4mA
20mA
0mA
20mA
0v
10V
Closing
counterclockwise
CI2701 board:
switch 7 on B
GAMK board:
switch 3 on B