Bernard Integral+ Commissioning Instructions page 39

Hide thumbs Also See for Integral+:
Table of Contents

Advertisement

Put back the 'potentiometer' board on the
camblock axis (if it has been dismounted for cam
adjustment).
Plug a milliamp-meter between terminals 31 and
32 to measure the position feedback.
Open the control box of the actuator to find the
positioner board (also called GAM-K)
Set the red knob on REMOTE position
Set the selector to 0%. The actuator will receive a
closure command (equivalent to 4mA command).
Case N°1: The actuator runs in closing direction
and stops before reaching the limit switch.
Turn the actuator's potentiometer gradually to
bring the actuator on the limit switch. Then turn
slowly the potentiometer in reverse up to turn the
red light off.
Case N°2: The actuator runs in closing direction
and stops on the limit switch and the red 'close'
light remains ON.
Slowly turn the actuator's potentiometer up to
turn the red light off.
Set the selector to 100%. The actuator will
receive an order for opening (equivalent to 20mA
command).
Case N°1: The actuator runs in opening direction
and stops before reaching the limit switch. Adjust
the board potentiometer "ADJ 100%" gradually
in CW direction to bring the actuator on the limit
switch.
Slowly turn the board potentiometer in CCW
direction to turn the green light off.
Case N°2: The actuator runs in opening direction
and stops on the limit switch and the green 'open'
light remains ON.
Turn slowly the board potentiometer "ADJ 100%"
in CCW direction to turn the green light off.
Check the repeatability of the setting by several
strokes 0% > 100% then set the selector to
AUTO
Adjustment of POSIGAM+
31(-) and 32(+)
This board is located
at 90 ° of the local
command.
Local command is now
impossible
Actuator is running is
closing direction
The 0% is now
synchronized.
Check the position
signal measured
between 31 and 32
(4mA depending on
the configuration)
Actuator is running is
opening direction
The 100% is now
synchronized.
ADJ
100%
Check the position
signal measured
between 31 and 32
(20mA depending on
the configuration)
Set-up is completed
INTEGRAL+ / POSIGAM +
Fast set up